 C-TRIP CHARACTERISTICS
Application Examples:
ONE POLE
ONE POLE PLUS NEUTRAL
Low inrush motors, lighting, wiring protection, appliances, business equipment, and control circuit applications. Relatively long thermal trip delay and medium magnetic trip point.
1C
Rated Current Type/ Cat. No. 1CU03 1CU05 1CU075 NA 1CU1 1CU1.6 1CU2 1CU2.5 1CU3 1CU3.5 1CU4 1CU5 1CU6 1CU8 1CU10 NA NA 1CU13 1CU15 1CU16 1CU20 1CU25 1CU30 1CU32 1CU40 1CU50 1CU60 1CU63 Approvals
UL UL UL
2CN
Type/ Cat. No. 2CNU03 2CNU05 2CNU075 NA 2CNU1 2CNU1.6 2CNU2 2CNU2.5 2CNU3 2CNU3.5 2CNU4 2CNU5 2CNU6 2CNU8 2CNU10 NA NA 2CNU13 2CNU15 2CNU16 2CNU20 2CNU25 2CNU30 2CNU32 2CNU40 2CNU50 2CNU60 2CNU63 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Approvals
UL UL UL
Type Designation 2 -- (a) C -- (b) N -- (c) U -- (d) 60 -- (e)
(a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current
Approvals:
UL508 Listed
0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 277VAC
UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL
* * * *
* * * *
Voltage Rating Interrupting Capacity (UL/CSA - Ratings) Group Short Circuit (UL/CSA - Ratings) Interrupting Capacity (VDE - Ratings) Mechanical Endurance Calibration Temperature Standard Pack and Weight Terminal Size Acceptability Terminal Torque Basic Dimensions (Elevation View)
Not European standard rating. Please refer to page 21 for specific
0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
applications. DC rating (Manufacturer's self certification): One pole 48VDC, two pole series 125VDC * VDE pending
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 10
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm (1.38 in.)
2C
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A Type/ Cat. No. 2CU03 2CU05 2CU075 NA 2CU1 2CU1.6 2CU2 2CU2.5 2CU3 2CU3.5 2CU4 2CU5 2CU6 2CU8 2CU10 NA NA 2CU13 2CU15 2CU16 2CU20 2CU25 2CU30 2CU32 2CU40 2CU50 2CU60 2CU63 Approvals
UL UL UL
3C
Type/ Cat. No. 3CU03 3CU05 3CU075 NA 3CU1 3CU1.6 3CU2 3CU2.5 3CU3 3CU3.5 3CU4 3CU5 3CU6 3CU8 3CU10 NA NA 3CU13 3CU15 3CU16 3CU20 3CU25 3CU30 3CU32 3CU40 3CU50 3CU60 3CU63 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
Seconds
70 mm (2.76 in.)
Approvals
UL UL UL
V-EA-C Trip 0.3A Through 10A Rated Current
1.13-1.45xIN
60 40
Minutes
10 4 1
Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC
UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL
Tripping time t
10 4 1 0.4 10-1 4x10-2
Seconds
UL UL UL
10-2 4x10-3 10-3
1
2
3 4 5 6 8 10
20
40
100
UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL
Multiple of Rated Current
V-EA-C Trip 13A Through 63A Rated Current
1.13-1.45xIN 60 40
* * * *
* * * *
Minutes
10 4 1
Thermal Overload "Must Trip" < 1 hr = 145% RC "Must Not Trip" > 1 hr = 113% RC
Tripping time t
10 4 1 0.4 10-1 4x10-2 10-2 4x10-3 10-3
480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 13-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/1.4kg (3.1 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
"C" Magnetic Trip Parameters Rated current 0.3A to 63A. 1. Hold for a minimum of 100ms at surge of 5 times rated current. 2. Trip in under 100ms at 10 times rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech.
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
35 mm (1.38 in.)
52.5 mm (2.07 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 11


▲Up To Search▲   

 
Price & Availability of 1CR5

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X